+48 52 382 44 50

Mixing valves MIX M

Description:

Mixing valves MIX M are used in central heating. Three-way mixing valve is used primarily to reduce the temperature of heating circuit such as floor heating systems. Four-way mixing valve in addition to temperature control circuit protects the boiler / heat source from a low return temperature. Fully automatic operation of the valve can be provided by the actuator from WOMIX like MP 10.

Technical data:


 

Dimension: from 3/4” to 2”
Seal:  two O-rings EPDM
Body:  brass Ms CW617N
Rotor and cap:  brass Ms CW617N
Angle of rotation:  90°
Max pressure:
 10 bar
Max temp.:  110° C
Handle:  red plastic
Scale: aluminium


Actuator:

 

for dimension 3/4” - 2” - MP 10

 

Construction of mixing valves MIX M:

Mounting the actuator MP 10 on mixing valve MIX M:



Dimensions:


3-way mixing valves


Typ
kv
Dimensions
A
B
C
D
S
M
E
Cod.
MIX M 3- 20       
4
3/4"
74
50
35,4
1832
6
80
601001
MIX M 3- 20
63/4"745035,4
1832680601002
MIX M 3- 2083/4"745035,41832680601003
MIX M 3- 25
81"805035,42040682601004
MIX M 3- 25
121"805035,42040682601005
MIX M 3- 32
121 1/4"
865035,42550687
601006
MIX M 3- 32
181 1/4"
865035,42550687601007
MIX M 3- 40
281 1/2"
1107039,42755697601008
MIX M 3- 50
442"1207039,427706107601009


4-way mixing valves


Type
kv
Dimensions
A
B
C
D
S
M
E
Cod.
MIX M 4- 20       
8
3/4"
74
50
35,4
1832
6
80
602003
MIX M 4- 25
81"805035,42040682602004
MIX M 4- 25
121"805035,42040682602005
MIX M 4- 32
121 1/4"
865035,42550687
602006
MIX M 4- 32
181 1/4"
865035,42550687602007
MIX M 4- 40
281 1/2"
1107039,42755697602008
MIX M 4- 50
442"1207039,427706107602009

Examples of applications of 3-way mixing valve

Diagrams and scale setting




Examples of applications 4-way mixing valve

Diagrams and scale setting